Service sizing is one of the first calculations in a house design, and one of the easiest to get wrong by adding up nameplates. NEC Article 220 gives a standard method that starts from the connected load and applies demand factors, because a house never runs every light, receptacle and appliance at once.
The standard method
General lighting is taken at 3 VA per square foot of living space. The kitchen needs at least two small-appliance circuits at 1,500 VA each (210.11(C)(1)) and the laundry one circuit at 1,500 VA (210.11(C)(2)). Those three loads together take the first 3,000 VA at 100 % and the remainder at 35 %.
Appliances
A range up to 12 kW counts as 8 kW of demand under Table 220.55 Column C. A dryer counts at its nameplate or 5,000 VA, whichever is larger. Fixed appliances such as the water heater and dishwasher are added in full, or at 75 % when there are four or more of them. Air conditioning is added at 100 %; where there is also electric heat, the larger of the two is used (220.60).
The service size
The demand load in VA divided by the service voltage gives the current, which is rounded up to the next standard size: 100, 125, 150, 200, 225, 250, 300, 350 or 400 A. Most new houses land at 200 A, and the trend to heat pumps and EV charging is pushing more of them to 400 A.
What it does not do
This is a simplified standard method. A full calculation adds space heating (220.51), the heat-versus-cooling comparison (220.60), EV charging, pool and spa equipment and any other special loads. The optional method (220.82) often gives a lower number and is worth running beside this one.